Gold Member Since 2017
Audited Supplier
Union Polymer Material Co., Ltd.

2.5: 1 Heat Shrink, Shrink Tube, Heat Shrinkable Tube manufacturer / supplier in China, offering 36kv Red Halogen Free Bus Bar Insulation Heat Shrink Tube, Hrht/ Hrsr 6 to 1 Shrink Ratio Heat Shrink Black Clear Tubing 87/14.5 115/19.2 Wind Power Cable, Identification Sleeve Military Grade Heat Shrinkable UV Protection Sleeve 135º C 3: 1 White Color Ladder Format and so on.

(/ )

Supplier Homepage Product Bus Bar Insulation Heat Shrink Sleeve 36kv Red Halogen Free Bus Bar Insulation Heat Shrink Tube

36kv Red Halogen Free Bus Bar Insulation Heat Shrink Tube

FOB Price: US $1-13 / Meter
Min. Order: 500 Meters
Min. Order FOB Price
500 Meters US $1-13/ Meter
Get Latest Price
Port: Dalian, China
Transport Package: Neutral Packaging
Payment Terms: L/C, T/T, Western Union

Request a custom order and have something just for you!

Send Customized Request
Basic Info
  • Model NO.: S1(n)-35
  • Type: Insulation Sleeve
  • Material: Rubber
  • Maximum Voltage: 36kv
  • Certification: UL, ISO9001
  • Brand: Upm Heat Shrink
  • Termal Endurance: -40~105°c
  • Cross Reference: Bbit
  • Heat Shock(200°c/4hrs): No Drop, No Flow
  • Origin: Dalian China
  • Application: Insulators, Switchgear Cabinet Bare Bus Bar
  • Chemistry: Organic Insulation
  • Thermal Rating: A 105
  • Classification: Organic Insulating Material
  • Color: Red
  • Shrink Ratio: 2.5:1
  • Halogen Free: RoHS Compliant
  • Holding Air Test: No Air Gap Between Bendings
  • Trademark: UPM
  • HS Code: 39173200
Product Description
S1(n)-35 Halogen Free Bus Bar Insulation Heat Shrink Tube 
 
Features
      Heavy wall cross-linked polyolefin    Operating temperature: -40~105 ºC
      Bus bar insulation and protection    Shrink temperature: 125 ºC
      Reduces bus bar clearance requirement      Shrink ratio: 2.5:1
      Halogen free, RoHS compliant      Voltage class: 36KV
      Protects against short circuit and electrical leakage caused by small animals
  
Technical Data
PropertyTest method          Values          
PhysicalTensile strengthASTM D2671   ≥14 MPa
 Breakdown elongationASTM D2671  ≥500%
 Aging  (136ºC/168hrs)               Tensile strengthASTM D2671   ≥12 MPa
Breakdown elongationASTM D2671 ≥400%
Long term aging            
 (120ºC/3000hrs)         Breakdown elongationIEC 60684-2  ≥175%
Resistance to selected fluids  Tensile strengthIEC 60684-2   ≥8MPa
 (23ºC/168hrs)           Breakdown elongationIEC 60684-2   ≥250%
 Density ASTM D26710.95~1.05
 Thermal endurance IEC 216105 ºC
 Water absorption (23ºC/336hrs)ASTM D570    ≤0.2%
 Low temperature flexibility      (-40ºC/4hrs)ASTM D2671No cracking
 Heat shock (200ºC/4hrs)ASTM D2671No drop, No flow,No cracking  
 Holdig air test more than 3 After shrink, no air gap
 bendings on bus bar between H.S.T. and bus bar 
 Cutting test (110ºC/168hrs)Raychem method5mm Length cutting along longitudinal, 
no cracking 
 Halogen free IEC 61249-2-21Cl:900ppmmax.Br: 900ppmmax.
 Total(Cl + Br):1500ppm max.
ElectricalVolume resistivityASTM D2671≥1012 Ω.cm
 Tracking and erosion resistanceASTM D2303After 1h at 2.5kV
 or 1h at 2.75kV no tracking
 Dielectric strength(in insulation oil)ASTM D2671   ≥16 KV/mm
Chemical Color fastness to lightIEC 60684-3Compare between exposed and unexposed
 parts 
the color does not change
 Copper corrosion(158ºC/168hrs)IEC 60684-3Pass
Dimensions
ReferenceAs supplied(mm)After recovered(mm)Standard length
UPM S1(n)-35ID min.ID max.WT nom.m/spool
25/1025103.515 
30/1230123.615 
40/1640163.615 
50/2050203.615 
65/2565253.615 
75/3075303.715 
85/3585353.715 
100/40100403.715 
120/50120503.815 
150/60150603.815 
175/75175753.815 
Product selection
Bus bar size (mm)Single layer bus bar Two layers bus bar
20×3,25×3Φ25/10Φ30/12
30×3,30×4Φ30/12Φ40/16
30×10,40×4Φ40/16Φ50/20
40×10,50×5,50×6Φ50/20Φ65/25 (Φ75/30)
50×8,50×10,60×6,60×8Φ65/25 (Φ75/30)   Φ75/30(Φ85/35)
60×10,80×6,80×8,80×10Φ75/30(Φ85/35)   Φ100/40(Φ120/50)
100×8,100×10,100×12Φ100/40(Φ120/50)    Φ120/50
100×15,120×10,120×12,120×15Φ120/50     Φ150/60
150×12,150×15Φ150/60     Φ175/75
 
ID=Internal DiameterWT=wall thickness
Typical application
      Suitable for insulation and protection of bus bar against  accidental flashover up to 36 KV
      Ideal for using in switchgears cabinets or distribution board where space is limited and air
        spacing between bus bars need to be kept at minimal
Ordering 
     Standard color : Red
     Standard packaging on spools.
     Please specify specification, color, quantity when ordering
Cross reference
Raychem/ Tyco : BBIT
Send your message to this supplier
Avatar
Ms. Lily
Sales Manager for L. V. Dep.
*From:
To: Ms. Lily
*Message:

Enter between 20 to 4,000 characters.

This is not what you are looking for? Post a Sourcing Request Now

Find Similar Products By Category